HOME > Product Info > R-type Receiver > R-type

R-type

R-type receiver

CNS-2100 (R-type)

Description

It is designed capable of displaying to LCD data on various detectors/equipments the receiver works on, as well as fault situation such as power loss, errors in CPU, Module communication or print. It receives signals indicating the status of fire detection, device manipulation and operational condition, and diagnoses/displays impaired conditions such as circuit disconnection, short circuit, Module failure, etc. It also monitors unserviceable device condition and abnormality of communication.

Type No Su-05-3-2
Operational voltage AC 220V 60Hz
Through current 50mA
Model type DC 24V, semiconductor type, digital type, LCD type
Ambient condition -10¡É~50¡¯C, 90%RH
Max links 64 systems
Communication type CAN PROTOCOL
Size 600mm(W) * 2000mm(H) *600mm(D) (H wheel included: 2000mm)
Total number of Module outputs that can be accommodated 96 Modules/system
Number of circuits 24,576 points for monitoring / 18,432 points for controling
Color 5Y7/1 (tailorable to customer need)